LON I/O-card to K3I 110
The K3I110 offers 16 inputs and outputs at the same time. The inputs
supervised on open circuit, short circuit, deviation and ground fault. The outputs
are triggered via potential free contacts (NO). All 16 in-/outputs are fully
programmable via PC. On the LON-bus, up to 16 (FC330A.) / 32 (FC700A)
in-/output cards can be connected.
Equipped with mounting plate for the installation in the plastic housing H23G230.
For flush mounting use the H23G230, H23U230 and H23Z230.
| Operating voltage |
9... 45 VDC |
| Dimensions (W x H x D) |
122 x 220 x 45 mm |
| Programmable relay output |
16 |
| Contact rating (relay) |
30 VDC / 1 A |
| Programmable input |
16 |
| Quiescent current |
24 mA |
| Alarm current |
184 mA |