Call point "Heavy Duty" FDM223H
For the immediate manual actuation of a fire alarm. Indirect alarm actuation
by smashing in the glass plate and pressing the push button. To replace the
glass plate, open the housing door with the key. The push button must be set
back before closing the door again.
For indoor and outdoor application, equally suited for wet, humid and dusty
areas. Only for surface mounted feed lines in easily accessible places, e.g.
Tunnels, Industry.
The housing is equipped with one opening at the top and two openings at the
bottom for locking plugs and for metal screwed cable glands M20.
For IP64 applications the unused openings must be locked with the V-plug.
The housing FDMH292-R and the electronic unit FDME223 must be
ordered separately.
| Operating temperature |
-25... +70 °C |
| Relative humidity |
≤95 % (no condensation) |
| Data sheet |
008345 |
Accessories
|
DMZ1197-AD Protection seal ; DMZ1197-AC Protective cover ; A5Q00004478
Screwed cable gland M20 ; A5Q00010055 V-plug PA M20 |
| Dimensions (W x H x D) |
134.3 x 134.3 x 43.2 mm |
| Storage temperature |
-30... +75 °C |
| Protection category |
IP44 (IP64 with protection seal) |
| Standard |
EN54-11, EN54-17 |
| Approval |
VdS G205014, LPCB 126ap/09 |
| Communication protocol |
FDnet |
| Ext. alarm indicator |
2 |
| System compatibility |
FDnet -> FS20, AlgoRex, SIGMASYS |